Queendom Tools

SMACNA Duct Leakage Calculator

For tab technicians running a SMACNA leakage test on new duct before the system is handed over — enter the duct surface area and test pressure, pick the seal class and duct shape, and read the allowable CFM you must stay under during the duct-blaster test.

Duct Leakage Calculation

-- CFM

SMACNA Leakage Class (CL) Values

Seal Class Rectangular Duct Round or Flat Oval Duct
A 6 3
B 12 6
C 24 12

How to Use This Calculator

  1. Enter the duct surface area in sq ft for the section being tested.
  2. Enter the test pressure in in. w.g. (e.g. 1.0 or 2.0).
  3. Choose the seal class (A, B or C) and the duct shape (rectangular, or round or flat oval).
  4. Read the max allowable leakage in CFM, or type a custom CL in the override field to use a specified leakage class instead.

FAQ

Q: What formula does SMACNA use for duct leakage?
A: F = CL × P^0.65, expressed in CFM per 100 sq ft, where P is the test pressure in in. w.g.; total allowable leakage = CL × (Area ÷ 100) × P^0.65.
Q: What CL value do I use for rectangular versus round duct?
A: For rectangular duct the leakage class is 6, 12 or 24 for seal classes A, B and C; for round or flat oval duct it is 3, 6 or 12.
Q: Why is the leakage rate per 100 sq ft instead of total CFM?
A: Because F = CL × P^0.65 is defined per 100 sq ft of duct surface, so the calculator multiplies it by Area ÷ 100 to get the allowable CFM for your actual duct area.
Q: What happens if I enter zero area or zero pressure?
A: The calculator returns an error and no CFM value, because the formula needs an area and a pressure greater than zero to produce a meaningful allowable leakage.